Differential configuration notes
Differential capability exists between any two sensor types.
For all differential configurations, the input range is X to Y where
X = Sensor A minimum - Sensor B max.
Y = Sensor A maximum - Sensor B min.
Accuracy for differential configurations
If sensor types are similar (for example, both RTDs or both
thermocouples), the accuracy = 1.5 times worst case accuracy
of either sensor type. If sensor types are dissimilar (for example,
one RTD and one thermocouple), the accuracy = Sensor 1
Accuracy + Sensor 2 Accuracy.
Analog sensors 4–20mA
Two types of alarm levels are available with 4-20 mA sensors on
the 848T. These types must be ordered with the S002 option
code complete with an analog connector kit. The alarm levels,
accuracy for each type are listed in Table 3.
Table 3. Analog Sensors
Sensor option
Alarm levels Accuracy
4–20 mA
(Rosemount Standard)
3.9 to 20.8 mA ± 0.01 mA
4–20 mA (NAMUR) 3.8 to 20.5 mA ± 0.01 mA