December 2014
14
Quick Start Guide
N6 CSA Dust Ignition-proof and Non-Incendive
Certificate: 1261865
Applicable Standards: C22.2 25:1966, C22.2 30:1986, C22.2 94:1991, C22.2 142:1987,
C22.2 157:1992, C22.2 213:1987, CAN/CSA C22.2 0:2001, ANSI/ISA 12.27.01-2003,
C22.2 60529:2005
Non-Incendive for Class I, Division 2, Groups A, B, C, and D.
Enclosure Type 4X / IP66.
For use with Rosemount power module P/N 753-9220-0001 only.
Non-incendive when installed per Rosemount drawing 00849-1016.
Europe
I1 ATEX Intrinsic Safety
Certificate No.: Baseefa09ATEX0022X II 1G
Applicable Standards: EN 60079-0:2009, EN-60079-1:2009, EN 60079-11:2007
Ex ia IIC T5/T4 Ga
Special Condition for Safe Use (X):
1. The surface resistivity of the antenna is greater than one GΩ. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
IECEx
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 09.0004X
Applicable Standards: IEC 60079-0:2009, IEC 60079-1:2009, IEC 60079-11:2007
Ex ia IIC T5/T4 Ga
Special Condition for Safe Use (X):
1. The surface resistivity of the antenna is greater than one GΩ. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
U
o
= 6.6 V
I
o
= 3.2 mA
P
o
= 5.3 mW
C
o
= 22 uF
L
o
= 1 H
U
o
= 6.6 V
I
o
= 3.2 mA
P
o
= 5.3 mW
C
o
= 22 uF
L
o
= 1 H