Rosemount 848T Especificaciones Pagina 115

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 136
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 114
105
Reference Manual
00809-0100-4697, Rev GA
Appendix D: Function Blocks
November 2014
Function Blocks
L_TYPE
Select Direct when the measurement is in the desired engineering units for the block
output. Select Indirect when converting the measured variable into another, for example,
pressure into level or flow into energy.
SCALING
XD_SCALE provides the range and units of the measurement and OUT_SCALE provides the
range and engineering units of the output. OUT_SCALE is only used when in indirect or
indirect square root.
D.1.2 AI block troubleshooting
Symptom Possible causes Corrective action
Mode will not leave
OOS
Target mode not set Set target mode to something other than OOS.
Configuration error BLOCK_ERR will show the configuration error bit
set. The following are parameters that must be set
before the block is allowed out of OOS:
• CHANNEL must be set to a valid value and cannot be
left at initial value of 0.
•XD_SCALE
.UNITS_INDEX must match the units in the
transducer block channel value. Setting the units in
the AI block automatically sets them in the
XD_BLOCK.
• L_TYPE must be set to Direct, Indirect, or Indirect
Square Root and cannot be left at initial value of 0.
Resource block The actual mode of the Resource block is OOS. See
Resource Block Diagnostics for corrective action.
Schedule Block is not scheduled and therefore cannot execute
to go to Target Mode. Typically, BLOCK_ERR will
show “Power-Up” for all blocks that are not
scheduled. Schedule the block to execute.
Process and/or block
alarms will not work.
Features FEATURES_SEL does not have Alerts enabled. Enable
the Alerts bit.
Notification LIM_NOTIFY is not high enough. Set equal to
MAX_NOTIFY. Alarm not linked to host.
Status Options STATUS_OPTS has Propagate Fault Forward bit set.
This should be cleared to cause an alarm to occur.
Value of output does
not make sense
Linearization Type L_TYPE must be set to Direct, Indirect, or Indirect
Square Root and cannot be left at initial value of 0.
Scaling Scaling parameters are set incorrectly:
• XD_SCALE.EU0 and EU100 should match that of the
transducer block channel value.
•OUT_SCALE
.EU0 and EU100 are not set properly.
• Both STB on each ASIC used must by in auto.
Cannot set HI_LIMIT,
HI_HI_LIMIT, LO_LIMIT,
or LO_LO_LIMIT Values
Scaling Limit values are outside the OUT_SCALE.EU0 and
OUT_SCALE
.EU100 values. Change OUT_SCALE or
set values within range.
Vista de pagina 114
1 2 ... 110 111 112 113 114 115 116 117 118 119 120 ... 135 136

Comentarios a estos manuales

Sin comentarios