20
Reference Manual
00809-0100-4697, Rev GA
Section 3: Configuration
November 2014
Configuration
3.2 Configuration
3.2.1 Standard
Each FOUNDATION
™
fieldbus configuration tool or host system has a different way of displaying
and performing configurations. Some will use Device Descriptions (DDs) and DD Methods to
make configuration and displaying of data consistent across host platforms.
Unless otherwise specified, the 848T will be shipped with the following configuration (default):
Table 3-1. Standard Configuration Settings
Refer to that systems documentation to perform configuration changes using a F
OUNDATION
fieldbus host or configuration tool.
Note
To make configuration changes, ensure that the block is Out of Service (OOS) by setting the
MODE_BLK.TARGET to OOS, or set the SENSOR_MODE to Configuration.
3.2.2 Transmitter configuration
The transmitter is available with the standard configuration setting. The configuration settings
and block configuration may be changed in the field with the Emerson Process Management
Systems DeltaV
™
, with AMS
®
inside, or other FOUNDATION fieldbus host or configuration tool.
3.2.3 Custom configuration
Custom configurations are to be specified when ordering.
3.2.4 Methods
For FOUNDATION fieldbus hosts or configuration tools that support device description (DD)
methods, there are two configuration methods available in the transducer block. These
methods are included with the DD software.
Sensor Configuration
Sensor Input Trim (user input trim)
See the host system documentation for information on running DD methods from the host
system. If the F
OUNDATION fieldbus host or configuration tool does not support DD methods,
refer to “Block configuration” on page 25 for information on how to modify sensor
configuration parameters.
Sensor Type
(1)
(1) For all eight sensors
Type J Thermocouple
Damping
(1)
5 seconds
Measurement Units
(1)
°C
Output
(1)
Linear with Temperature
Line Voltage Filter
(1)
60 Hz
Temperature Specific Blocks
• Transducer Block (1)
FOUNDATION fieldbus Function Blocks
• Analog Input (8)
•Multiple Analog Input (2)
• Input Selector (4)