71
Reference Manual
00809-0100-4697, Rev GA
Appendix B: Product Certifications
November 2014
Product Certificates
I6 CSA Intrinsically Safe and Division 2
Certificate: 1261865
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91, CSA Std.
C22.2 No. 142-M1987, CSA Std. C22.2 No. 157-92, CSA Std. C22.2 No.
213-M1987, CSA Std. C22.2 No. 60529:05
Markings: Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D; T3C (-50 °C ≤ Ta ≤
+60 °C) when installed per Rosemount drawing 00848-4405; Class I, Division
2, Groups A, B, C, D; T3C (-50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405
IF CSA FISCO
Certificate: 1261865
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91, CSA Std.
C22.2 No. 142-M1987, CSA Std. C22.2 No. 157-92, CSA Std. C22.2 No.
213-M1987, CSA Std. C22.2 No. 60529:05
Markings: Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D; T3C (-50 °C ≤ Ta ≤
+60 °C) when installed per Rosemount drawing 00848-4405; Class I, Division 2,
Groups A, B, C, D; T3C (-50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405
N6 CSA Division 2 and Dust-Ignition-proof (enclosure required)
Certificate: 1261865
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std. C22.2 No. 30-M1986, CAN/CSA
C22.2 No. 94-M91, CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2 No.
213-M1987, CSA Std. C22.2 No. 60529:05
Markings: Class I, Division 2, Groups A, B, C, and D; T3C (-50 °C ≤ Ta ≤ +60 °C) when
installed per Rosemount drawing 00848-4405; Dust-Ignition-proof for Class II,
Division 1, Groups E, F, and G; Class III; Conduit Seal Required
B.4 Europe
I1 ATEX Intrinsic Safety
Certificate: Baseefa09ATEX0093X
Standards: EN 60079-0:2012, EN60079-11:2012
Marking II 1 G Ex ia IIC T4 Ga (-50 °C ≤ Ta ≤ +60 °C) when installed per drawing
00848-4406
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a degree of
protection of at least IP20. Non-metallic enclosures must be suitable to prevent
electrostatic hazards and light allow or zirconium enclosures must be protected
from impact and friction when installed.
2. The equipment is note capable of withstanding the 500V insulation test required
by EN 60079-11:2012, clause 6.3.13. This must be taken into account when
installing the equipment.